4 Web Interface – Integration Version
If a sensor needs to be edited or manually entered, click the sensor’s system number
(identifier) # link—displayed in blue and underlined to the left of each sensor row.
Figure 4.4
Editing Sensor Properties
Click the number in the left side of the sensor row to edit individual sensor properties.
Figure 4.5
Wireless Sensor Configuration
For each sensor, you can edit all fields in gray. All other fields are for reference. To the right of
the Value field is the corresponding Modbus Register for slave data output from that sensor.
To the right of that is the BACnet Instance number for slave interface to a Building
Management System.
Click on a sensor number to edit.